Inspection Information
Facility Name: Fairfield Inn
Facility Type: Pool
[?] Inspection type: Standard
Inspection date: 26-April-2022
Violations: A summary of the violations found during the inspection are listed below.
3701-31-04 (B)(6)
At the time of inspection, one of the skimmers was observed without a weir. To properly filter the surface of the pool, a weir is required. Install a weir.

3701-31-04 (B)(6)(f)
Repeat At the time of inspection, the flow was observed at approximately 25 gallons per minute. To ensure the entire volume of the pool is turned over every 8 hours, increase the flow to at least 32 gpm. When increasing the flow, ensure it doesn't exceed 48 gpm.

3701-31-04 (C)(3)
At the time of inspection, the total alkalinity was observed at 30 ppm. To ensure the pool is properly balanced, increase the total alkalinity to at or above 60 ppm.

Comments
- Ensure the flotation device is in good repair and the rope is adequate length (30 ft - 60 ft).