Inspection Information | Facility Name: | Troy Country Club (Wading) |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 23-May-2019 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6)(h) The flow meter in the pump room was observed in disrepair - not reading flow. To ensure proper flow, replace or repair the flow meter. |
3701-31-04 (B)(6)(p) Around the pool, the deck was observed with cracks that could result in standing water. To prevent any standing water, fill in the cracks or replace. |
3701-31-04 (C)(2) At the time of inspection, the pH was observed at 7.0. For the chlorine to properly disinfect the pool, the pH shall be between 7.2 and 7.8. Increase the pH of the pool. |
Comments |
---|
- At the time of inspection, all the safety equipment was present and in good repair. Also, the chlorine was observed within normal limits. The pool is satisfactory to operate. |