Inspection Information | Facility Name: | Comfort Suites |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 24-April-2018 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 ( D )(6)(a) At the time of inspection, the ORP was observed at 348. To allow for proper chlorine concentration, the ORP shall be at or above 650. Increase the ORP. |
3701-31-04 (B)(1)(c) Critical At the time of inspection, the free chlorine was observed at 0.0 ppm. For the pool to be properly disinfected, the free chlorine shall be at or above 1.0 ppm. Increase the free chlorine to at or above 1.0 ppm. |
3701-31-04 (B)(1)(e) Critical At the time of inspection, the ORP reading was observed at 348 and the free chlorine was observed at 0.0 ppm. To ensure proper chlorine concentration, the Automatic Chemical Controller shall be maintained in good repair. Repair or replace the ACC to ensure the ORP is at or above 650 and the free chlorine is at or above 1.0 ppm. |
3701-31-04 (B)(6)(h) The flow meter was observed at 0.0. To ensure proper flow, the flow meter shall be maintained in good repair. Have the flow meter repaired or replaced. |
Comments |
---|
- At the time of inspection, all the safety equipment was present. - Cease operation of the pool until the free chlorine is at or above 1.0 ppm and the automatic chemical controller is working properly. |