Inspection Information | Facility Name: | Village of Concord |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 27-August-2018 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (C)(2) Repeat At the time of inspection, the pH was observed at 7.0. For the chlorine to properly disinfect the pool, the pH shall be between 7.2 and 7.8. Increase the pH of the pool water. |
3701-31-04 (C)(3) Repeat The total alkalinity was observed at 20 ppm. To ensure the pool is balanced, the alkalinity shall be at or above 60 ppm. Increase the alkalinity of the pool. |
3701-31-04 (E)(2)(a)(ii) Repeat At the time of inspection, a ring buoy was not observed in the pool area. To ensure a water rescue is able to be conducted, a ring buoy shall be present. Provide a ring buoy with a 30 - 60 ft line. |
3701-31-04 (E)(2)(a)(iii) Repeat In the pool area, a back/spine board was not observed. To allow for proper back support in an emergency, a back/spine board shall be present. Provide a back/spine board. |