Inspection Information | Facility Name: | Tipp Aquatic Center (Spray Ground) |
---|---|
Facility Type: | Special Use Pool |
[?] Inspection type: | Follow-up |
Inspection date: | 28-May-2021 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6)(x) Repeat At the time of inspection, there was large amounts of debris on the spraygrounds. Ensure the sprayground is free of any organic material. |
The following violation(s) have been corrected since the last inspection. |
---|
3701-31-04 (B)(6)(p)/Deck surfaces are free of standing water or other hazards. While the sprayground was functional, observed drains backing up leading to standing water on the deck. Ensure the drains are clean and functional. |
3701-31-04 (C)(2)/pH is within 7.2 to 7.8 At the time of inspection, the pH was observed above 8.0. Ensure the pH is between 7.2 and 7.8. During this inspection, the free chlorine was observed around 50 ppm. Prior to lowering the pH, ensure the free chlorine is reduced. |
Comments |
---|
Chlorine level was at a readable number at 6.2. Observed organic or dirt debris being pushed into the slide activity area. This splash ground is taking in a lot of dirt, operation must control with amount of dirt entering the system. Future problems will occur if this not figure out. |