Inspection Information | Facility Name: | Troy Country Club (Wading) |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Follow-up |
Inspection date: | 02-June-2022 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6)(h) Repeat Observed the circulation pump flow meter non-functional. Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation. |
3701-31-04 (B)(6)(p) Repeat Deck surfaces had standing water or other hazards. Observed rubber deck surface degraded. Upon re-inspection, the rubber deck was observed in progress undergoing repairs. Repair areas of the deck where standing water is occuring. If more than 50% of the deck must be replaced, plans must be submitted to the Ohio Department of Health for review and approval. |
3701-31-04 (E)(3)(b) Repeat The unguarded pool was observed without the "Children must be supervised" and/or "Swimming alone is not recommended" signs posted. Post the "Children must be supervised" and/or "Swimming Alone is Not Recommended" signs at all times the pool is available for use. |
3701-31-04(D)(6)(a)(2) Critical Repeat Pool free chlorine disinfectant residual was below 1 ppm. Free chlorine observed at 0 ppm. Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above. |
Comments |
---|
At the time of inspection, the free chlorine for the wading pool was observed at 0ppm. Miami County Public Health (MCPH) suspects that because the main pool (chlorine of 6.4) and wading pool are under the same chlorinating system, that there is some malfunction in the system causing the wading pool to not take in any chlorine. Due to this, the wading pool shall not be operated until a representative from MCPH verifies a chlorine level of 1 ppm or higher. When the chlorine level has been tested to be at 1 ppm or above, call our department and inform us, so that we may verify it upon inspection. Inspection conducted with Brittney Holbrook. |