Inspection Information | Facility Name: | Home 2 Suites |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 01-November-2023 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(4)(c) Repeat According to the records provided, the automatic chemical controller (ACC) and safety vacuum release system (SVRS) were observed not tested monthly. To ensure proper function, the ACC and SVRS shall be tested and documented monthly. Ensure the ACC and SVRS are tested and documented monthly |
3701-31-04 (B)(6) Repeat At the time of inspection, the measured flow rate (70 gallons per minute) exceeded the manufacturer's maximum filter flow rate (68 gallons per minute). To ensure proper function, equipment shall be maintained per manufacturer's specifications. Evaluate the system and decrease flow. |
Comments |
---|
- At the time of inspection, all the safety equipment were observed and in good repair. Also, water quality readings were observed within normal limits. |