Inspection Information | Facility Name: | Tecumseh Woods Inc, Inc-Wading |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 23-August-2023 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6)(h) Repeat At the time of inspection, the flow meter was observed nonfunctional. To ensure the turnover rate meets the requirement, the flow meter shall be functional. Repair or replace the flow meter. |
3701-31-04 (C)(3) Repeat At the time of inspection, the total alkalinity was observed at 50 ppm. To ensure the pool water is balanced, the alkalinity shall be at or above 60 ppm. Increase the total alkalinity to or above 60 ppm. |
Comments |
---|
- Ensure the safety vacuum limit system (SVRS) is tested on a monthly basis and documented. Also, ensure any corrective actions to improper water quality readings are documented. - At the time of inspection, all safety equipment was present and in good repair. - Inspection was conducted with Taylor Munn |