Inspection Information
Facility Name: Tipp Aquatic Center (Lap)
Facility Type: Pool
[?] Inspection type: Standard
Inspection date: 21-August-2023
Violations: A summary of the violations found during the inspection are listed below.
3701-31-04 (B)(6)
At the time of inspection, the flow was observed at 1083 gallons per minute while the maximum flow rate of the filters was observed at 789 gallons per minute.
Ensure the flow rate doesn't exceed the flow rate of the filter manufacturer's specifications.
3701-31-04 (C)(2)
At the time of inspection, the pH was observed at 7.0.
For the chlorine to properly disinfect the water, the pH shall be between 7.2 and 7.8. Increase the pH.
3701-31-04 (C)(3)
At the time of inspection, the alkalinity was observed at 50 ppm.
To ensure the water is balanced, the total alkalinity shall be at or above 60 ppm. Increase the alkalinity to or above 60 ppm.
Comments
- Ensure the bags of sodium bicarbonate (base) and bottles of pH down (acid) are separated.

- The inspection was performed in conjunction with Brittney Holbrook.