Inspection Information | Facility Name: | Tipp Aquatic Center (Lap) |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 10-August-2016 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(6)(p) Deck surfaces has chipping and cracking surfaces. Repair areas of the deck where standing water is occuring. If more than 50% of the deck must be replaced, plans must be submitted to the Ohio Department of Health for review and approval. |
3701-31-04 (D)(8)(a) DPD test kit was not used for testing water quality. Visual chlorine test being used to monitor chlorine levels in lap pool. Obtain a DPD test kit to test water quality of the pool. |
Comments |
---|
In pool records, there some concern about chlorine levels. Ensure an accurate test kit is used and that chlorine levels are above 1 ppm at all times before opening. |