Inspection Information | Facility Name: | Dolphin Club |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 26-June-2023 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 (B)(4)(a)(iv) Water temperatures were not being recorded daily. Ensure pool water temperatures are recorded at least once daily. Take and record the water temperature at least once/day. |
3701-31-04 (B)(4)(a)(vi) Total alkalinity was not tested/recorded weekly. Ensure total alkalnity is tested and recorded weekly. Test and record total alkalinity at least once/week. |
Comments |
---|
At time of inspection, Automatic Chemical Controller was reading no-flow while there was flow through the system (flow observed on flow meter). Ensure facility is testing water chemistry at least every 4 hours while the facility is open. The facility is now manual dosing with the chemical feeders dosing a small amount of acid and chlorine disinfectant at regular intervals. A reinspection will occur on or after 06/28/23 or when the Automatic Chemical Controller is fixed and able to be checked, tested, and a valid ORP value recorded. |