Inspection Information | Facility Name: | Ohio Health Mansfield Hospital |
---|---|
Facility Type: | Commercial FSO < 25000 sq. ft. |
[?] Inspection type: | Standard/Critical Control Point |
Inspection date: | 10-January-2020 |
Violations: A summary of the violations found during the inspection are listed below. |
3717-1-05.1(C)(1) / Handwashing sink - required water temperature Handwashing sink water below 100°F. Women's rest-room by walk in coolers had a temperature of 96F. Please repair or adjust so unit is above 100F.by next standard inspection. Correct By: 10-Feb-2020 |
3717-1-06.2(E) / Handwashing signage. Corrected During Inspection Handwashing sign(s) not posted. Handwashing signs were missing in satellite kitchens A40 and A32. PIC had posted. |
3717-1-05.1(O)(2) / Using a handwashing sink - other uses prohibited. Critical Repeat Corrected During Inspection Handwashing sink is being used for purposes other than handwashing. Hand wash sink in satellite kitchen A47 had cup in sink and B21 had food debris in it, also OB kitchen had sanitizer bucket. PIC had items removed and sinks are cleaned. |
3717-1-04.5(B)(5) / Equipment food-contact surfaces and utensils - cleaning frequency. Utensils and equipment contacting non-TCS foods not cleaned at required frequency. Water dispenser nozzle in ice machine in dining room had calcium accumulation. Please clean. Correct By: 11-Jan-2020 |
3717-1-04.5(B)(5) / Equipment food-contact surfaces and utensils - cleaning frequency. Utensils and equipment contacting non-TCS foods not cleaned at required frequency. Ice chute on ice machine in dining room had black mold build up. Please clean. Correct By: 11-Jan-2020 |
3717-1-04.4(O) / Manual warewashing equipment - chemical sanitization using detergent-sanitizers Corrected During Inspection Detergent-sanitizer applied in sanitizing step is not the same as detergent-sanitizer used in washing step. Using two compartment sink for warewashing without using detergent sanitizer. PIC stated they will no longer use sink for warewashing. |
3717-1-03.2(Q) / Food storage - preventing contamination from the premises. Corrected During Inspection Improper storage of food items. Soda cans and water bottles stored under paper towels and soap for hand sink, exposed to splash. PIC had moved. |
3717-1-03.2(Y) / Miscellaneous sources of contamination. Corrected During Inspection Food not protected from contamination. Hobart mixer had seal leaking gear grease. PIC removed from service till repaired. |
3717-1-03.2(Y) / Miscellaneous sources of contamination. Corrected During Inspection Food not protected from contamination. Two personal drinking bottles found in four door freezer and personal partially consumed ice cream in A37 freezer. PIC had removed. |
3717-1-04.8(E)(2) / Clean equipment and utensils stored in a self-draining position and covered or inverted. Repeat Clean equipment and utensils not stored in a self-draining position and covered or inverted.Clean dinner ware not stored inverted or protected. |
3717-1-04.8(G)(1) / Kitchenware and tableware - handling of single-service and single use articles. Repeat Corrected During Inspection Single-service or single-use articles, kitchenware, or tableware not handled, displayed, or dispensed properly. Thongs in coffee corner were not stored with handles displayed and single use utensils in A40, A47, A32 were not stored in an inverted manner. |
3717-1-04.1(C) / Food-contact surfaces - cleanability Critical Corrected During Inspection Food contact surfaces not easily cleanable. Black rubber for pepper dicer was missing teeth. PIC removed from service till repaired. |
3717-1-04.4(A)(2) / Equipment components kept intact, tight, and adjusted Corrected During Inspection Equipment components are not intact, tight or properly adjusted. Crescore left side exterior had hole with exposed insulation. |
3717-1-04(A) / Multiuse utensils and food contact surfaces - material characteristics. Critical Corrected During Inspection Equipment and/or utensils improper construction. Posters taped to equipment, rendering them no longer easily cleanable. |
3717-1-04.1(H) / Nonfood-contact surfaces - cleanability Nonfood-contact surfaces not easily cleanable. Scoop holders for flour, oatmeal and rice are caulked to the top of the lids rendering them no longer easily cleanable. |
3717-1-04(A) / Multiuse utensils and food contact surfaces - material characteristics. Critical Corrected During Inspection Equipment and/or utensils improper construction. Towels used to soak up food debris under egg scrambling grill. |
3717-1-04.4(A)(2) / Equipment components kept intact, tight, and adjusted Equipment components are not intact, tight or properly adjusted. Gaskets torn on doors of the following equipment: Kitchen A30 both freezer doors and lower cooler door, coffee corner reach in cooler, expo reach in #2, alto sham halo heat, crescore hot holding gasket, Vulcan seal and faceplate torn, walk in dairy cooler. Pleas have repaired or replaced by next standard inspection. |
3717-1-04.1(C) / Food-contact surfaces - cleanability Critical Food contact surfaces not easily cleanable. Cracked arm on third small cooking pot, coating coming off. |
3717-1-04.1(A) / Equipment and utensils - durability and strength. Non-durable equipment observed. Ice machine, outside of walk in coolers is not draining properly. |
3717-1-04.5(A)(3) / Cleanliness of nonfood-contact surfaces of equipment. Non-food contact surfaces of equipment are unclean. Expo reach in #1 fan guard had dust build up and crestcore hot holding unit had dust on fan guard. Please clean. |
3717-1-04.5(D) / Nonfood-contact surfaces - cleaning frequency. Non-food contact surface(s) not cleaned at the required frequency. Cook top on stove had excessive carbon build up. Correct By: 17-Jan-2020 |
3717-1-04.5(A)(3) / Cleanliness of nonfood-contact surfaces of equipment. Repeat Non-food contact surfaces of equipment are unclean. Both Vulcan ovens have excessive carbon build up on inside. Please clean. Correct By: 17-Jan-2020 |
3717-1-04.5(A)(3) / Cleanliness of nonfood-contact surfaces of equipment. Non-food contact surfaces of equipment are unclean. Juice machine in dining room has splash build up behind the nozzles. Please clean. Correct By: 11-Jan-2020 |
3717-1-04.5(A)(3) / Cleanliness of nonfood-contact surfaces of equipment. Non-food contact surfaces of equipment are unclean. In service freezer #1 had dirty gaskets. Please clean. Correct By: 17-Jan-2020 |
3717-1-04.5(D) / Nonfood-contact surfaces - cleaning frequency. Non-food contact surface(s) not cleaned at the required frequency. Table service dispenser on in service line had visible residue. Please clean. Correct By: 11-Jan-2020 |
3717-1-04.5(D) / Nonfood-contact surfaces - cleaning frequency. Non-food contact surface(s) not cleaned at the required frequency. South bend ovens had carbon build up. Please clean. Correct By: 17-Jan-2020 |
3717-1-06.4(H) / Cleaning and maintenance of plumbing fixtures. Plumbing fixtures unclean. Pipe out of two bay prep sink had visible build up and residue. please have clean before next standard inspection. |
3717-1-06.4(B) / Cleaning - frequency and restrictions. Facility not maintained clean. Several cabinets in satellite kitchens had visible debris under them. Please clean before next inspection. |
3717-1-06.4(B) / Cleaning - frequency and restrictions. Facility not maintained clean. Black mold on dairy cooler ceiling and on some of the knock out plugs, mold on fanguard on ceiling in catering and tray cooler. Please clean. Correct By: 17-Jan-2020 |
3717-1-06(A)(1) / Indoor areas - surface characteristics Repeat Floors, walls, and/or ceilings not constructed of approved materials. Acoustical tile in pizza prep area. When it becomes soiled or damaged shall be replaced with, non adsorbent, smooth, durable and easily cleanable surface. |
3717-1-06.4(B) / Cleaning - frequency and restrictions. Facility not maintained clean. Pizza prep area had excessive dust accumulation on acoustical tile and ceiling vent. Please clean. Correct By: 17-Jan-2020 |
3717-1-06.4(B) / Cleaning - frequency and restrictions. Facility not maintained clean. Mop sink needs cleaned. Correct By: 17-Jan-2020 |
3717-1-06.4(A) / Repairing. Physical facilities not maintained in good repair. Outlet cover missing in satellite kitchen A20. Please replace by next standard inspection. |
3717-1-06.1(I) / Light bulbs - protective shielding. No protective shielding on lights. Light shield in small food prep room was not installed properly. |
3717-1-06.4(D) / Cleaning ventilation systems, nuisance and discharge prohibition. Ventilation system not maintained. Air vents over frozen ice cream and handsink in the in service area had excessive dust. Air vent over room service prep table had excessive dust. Air vent over small food prep room had excessive dust. Please clean. Correct By: 17-Jan-2020 |
3717-1-04.2(D) / Ventilation hood systems - adequacy. Ventilation hood system not sufficient to prevent grease or condensation build-up. Vent hood over room service cook line had visible grease dripping onto floor and side of grill and cloth used in corner to control drippage Please repair by next inspection. |
3717-1-06.2(I)(3) / Lighting - intensity (50 FC) Light intensity less than fifty foot candles in required areas. One light out in each hood vent in cook area. Please repair or replace before next standard inspection. |
Comments |
---|
Conducted inspection with Joette Moore R.S., Tina, Rick Cortez and Gregory Brandes Director of food and Nutrition Services. Two compartment sink being used for produce prep without being air gapped. Do not utilize sink for produce prep till it has been properly air gapped. Emailed inspection. |
IV - P - Demonstration of Knowledge: The person in charge is Certified in Food Protection. IX - P - Highly Susceptible Populations: Unopened food packages are not re-served. III - P - Preventing Contamination by Hands: Observed food employee changing gloves when required. III - P - Preventing Contamination by Hands: Observed food employee washing hands when required. VI - P - TCS Food: Observed ready to eat TCS foods being properly date marked, and discarded when required. VII - Protection from Contamination: Equipment food-contact surfaces or utensils are dirty. VI - P - TCS Food: Observed hot foods being held at 135°F or above; cold foods being held at 41°F or below. IX - P - Highly Susceptible Populations: Pasteurized eggs are used if served partially cooked. II - P - Good Hygienic Practices: Food employee(s) were eating, drinking or using tobacco in designated area. IX - P - Highly Susceptible Population:The operation was serving pasteurized juices to highly susceptible population. III - P - Preventing Contamination by Hands: Observed food employee washing hands prior to donning single use gloves. V - P - Food from Approved Source: Observed foods being received at the proper temperature, in good condition, safe and unadulterated. VII - Protection from Contamination: Observed improper storage of food items. I - P - Employee Health: The operation had an employee health policy on file. X - P - Chemical: Toxic materials are properly identified and stored. VI - P - TCS Food: Raw animal food was being cooked to the required temperature. |