[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Observed the ORP to be 615 millivolts.
Have the ACC unit inspected to determine why the ORP is low. The pool's ORP will need to be maintained at or above 650 millivolts.
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Repeat Observed some of the ladders to easily shake and rattle.
Repair or replace the ladders so that they are secure and do not easily shake and rattle.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat Observed the pH to be approximately 8.0.
Treat the pool so that the pH is maintained between 7.2 and 7.8.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Follow-up

Inspection Date: 29-August-2023


The following violation(s) have been corrected since the last inspection.
Comments
At time of inspection observed the total chlorine to be approximately 1 ppm, and the free chlorine to be approximately 1 ppm. Pool is okay to be open.