3701-31-04 (B)(6)(p) / Deck surfaces are free of standing water or other hazards.
Repeat Deck surfaces cracked and missing grout.
Repair areas of the deck where standing water is occuring. If more than 50% of the deck must be replaced, plans must be submitted to the Ohio Department of Health for review and approval.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Observed back gate does not self close or lock. Areas of fence have large gaps at bottom.
3701-31-04 (B)(6)(z) / Special features are maintained in good repair and according to manufacturer specifications.
Special features were not maintained in good repair or in accordance with the manufacturer specifications. Wood poles and netting in need of repair. Blue matting by play area is torn.
Repair/maintain all the special features in good repair and in accordance with the manufacturer's specifications. If necessary, replace broken components.
Facility Type: Special Use
[?] Inspection Type: Standard
Inspection Date: 19-July-2019