[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Observed ORP reading was below 650 mv at time of inspection. The ORP reading at time of inspection was 100 mv.
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Observed pH was outside the range of 7.2 to 7.8 at time of inspection: pH was 8.
Treat the pool water so that the pH is within the acceptable range.
3701-31-04 (E)(2)(b)(ii) / A back/spine board with straps and head immobilizers
Observed a back/spine board with straps that was missing the head immobilizers at time of inspection.
Provide a back/spine board with straps and a head immobilizer at the pool at all times.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 18-August-2020