3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. Observed ORP reading of 635 at time of inspection.
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Corrected During Inspection Observed combined chlorine and total chlorine both at 0 at time of inspection. The license shall not operate a public swimming pol or portion thereof when an imminent health hazard is present including when the disinfection residual is less than what is required in accordance with paragraph (D)(6) of this rule (1). Operator began dumping chlorine in pool at time of inspection. Free Chlorine tested 1 and Total Chlorine tested 1.
Corrective Action: Ensure the minimum disinfection residual maintains minimum 1ppm.
3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection. Operator noted that probes are not functioning properly.
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation.
3701-31-04 (B)(1)(g) / Water clarity shall be sufficient to see the pool bottom (or Secchi disc).
Critical Water clarity was not sufficient to see the pool bottom (or Secchi disc). Could not see bottom of pool at time of inspection.
Do not operate the pool when water clarity is poor.
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation. Observed flow meter not working at time of inspection. Operator noted that plans to install new flow meter are scheduled.
Maintain all meters and gauges in a properly funtioning manner at all times while the pool is in operation.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8. Observed ACC reading pH at 3.2 at time of inspection. Manually tested pH and tested higher than 8.
Treat the pool water so that the pH is within the acceptable range.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 18-July-2023
Comments |
---|
Follow up inspection scheduled for 7/19/2023 to follow up on critical violations noted in report. Do not operate pool until critical operational items are resolved. |