3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Observed the ORP to be 640 mv.
Have the ACC unit inspected to determined why the ORP is low. The ORP of the pool is to be 650 mv or greater.
3701-31-04 (E)(2)(d) / First aid kit provided
Repeat The first aid kit was not easily visible from the swimming pool or easily accessible. Operation had posted a sign in the pool area that stated the first aid kit was at the front desk.
A first aid kit is to be provided in the swimming pool area such that it is easily visible and readily accessible.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 28-March-2024
Comments |
---|
Observed the pool's water to be cloudy but was still able to see the bottom of the pool and the pool's main drain cover. Ensure that the water clarity is improved to improve visibility in the water. If the water becomes less clear such that one can not see the drain outlet cover the pool will need to immediately close. The pool is open for thirteen & a half hours per day but the disinfectant residual is tested only once a day prior to bathers entering the pool/spa area. The pool's operator was made aware and stated that they would conduct a second test per day of the disinfectant residual. |