3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met. Observed turnover rate at 60 gpm at time of inspection, while minimum required turnover rate for the size of the pool is 94 gpm.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Gate is not self-closing and self-latching and lockable. Observed newly constructed and altered door with PIC at time of inspection. Gate can close, latch, and is lockable but is not self-closing and self-latching.
Corrective Action(s): Repair the gate to ensure it is self-closing and self-latching and lockable.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 05-July-2023
Comments |
---|
Call (330) 343-5555 ext. 1420 or email jsample@tchdnow.org with questions. |