3701-31-04 (B)(6)(aa) / The Diving area/components are in good repair. No alterations have been made without plan approval
Observer craked no diving sign on pool deck at time of inspection
Repair no diving sign to prevent safty hazard
3701-31-04 (B)(6)(p) / Deck surfaces are free of standing water or other hazards.
Observed cracked concrete surfaces by yellow slide at time of inspection.
Repair areas of the deck where standing water is occuring. If more than 50% of the deck must be replaced, plans must be submitted to the Ohio Department of Health for review and approval.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Observed hole in fence by slides at time of inspection.
Repair the perimeter barrier so that there are not any gaps greater than 4 inches anywhere along the barrier.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 12-June-2017
Comments |
---|
No violation at time inspection. Went over clean up procedure with Person in Charge( PIC) |