3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records. No records found for week of Oct 17 or Oct 24.
All facility records must be maintained and available for review upon request.
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladder to pool not sufficiently secured at the time of inspection.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
The test kit provided was not in good repair. Outdated test kit observed. Residue build-up observed in chemical test tube.
Maintain the test kit in good repair to conduct water quality tests.
3701-31-04 (E)(2)(a)(ii) / A USCG Type IV personal flotation device with 30 -60 foot throw line provided
A USCG Type IV personal flotation device with 30 -60 foot throw line was not provided at the unguarded pool. Less than 30 feet of line provided for flotation device.
Provide a proper floatation device at all times.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 25-October-2016