3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat The pool's ORP was 626 mv at time of inspection.
Have the ACC unit inspected to determined why the ORP is low. The pool shall have a minimum ORP of 650 mv.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Observed the pH of the pool to be approximately 8.0.
Treat & maintain the pool so that the pH is maintained between 7.2 and 7.8.
3701-31-04 (E)(2)(d) / First aid kit provided
Repeat A first aid kit was not visible and easily accessible at the pool area.
Provide a first aid kit in the pool area that is readily visible and easily accessible.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 28-March-2024
Comments |
---|
The pool is open for fourteen hours a day but the disinfectant residual is tested once a day prior to bathers entering the pools. The pool's operator was made aware and stated that they would conduct a second test per day of the disinfectant residual. |