3701-31-04 (B)(6)(l) / Secondary means of entrapment/evisceration prevention is provided
Repeat Secondary means of entrapment/evisceration prevention was not provided.
Submit plans to the Ohio Department of Health for review and approval for the secondary means that will be employed on the pool.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Gate on perimeter barrier is not self-latching. Correction: All gates or doors on perimeter barrier must be self-closing and self-lathing.
3701-31-04 (E)(3)(c) / Location of emergency telephone posted when the phone is not visible.
Sign indicating the location of the emergency device (telephone) was not provided and emergency device was not visible in the pool area.
Ensure that a sign informing patrons of the location of the emergency device is always visible in the pool area.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 16-June-2022
Comments |
---|
Operator is in the process of repairing the self-latching mechanism of gate. Will verify the gate is self-latching at the next standard inspection July 2022. Need verification from ODH engineering regarding SVRS for this specific pool; follow up with next standard inspection July 2022. Letter from TCHD will be sent to facility regarding requirement of SVRS. |