3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not functional at time of inspection.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm (40 ppm) at time of inspection.
Raise the total alkalinity to at least 60 ppm.
3701-31-04(D)(6)(a)(1) / Combined chlorine shall not exceed 1.0 ppm.
Combined chlorine was greater than 1.0 ppm (2 ppm) at time of inspection.
Treat the pool so that the combined chlorine is less than 1 ppm.
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 11-April-2017