No critical violations were documented at the time of inspection.
No violations were documented at the time of inspection.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 29-March-2024
Comments |
---|
No violations were documented at time of inspection. Section #5 - was unable to determine the flow in gallons per minute (gpm) using the pool's flow meter. Flow meter does not indicate units of measurement or that the unit is a flow meter. The pool is to maintain a minimum flow of 268 gpm. Obtain and be able to provide the flow meter's use instructions from the manufacturer or other materials from the manufacturer and be able to show that the flow meter is measuring flow and that the pool's flow is maintained at a minimum of 268 gpm. Section #19 - reagents that are not indicated for use in the test kit's instructions are being used to measure disinfectant residual. Person-in-charge will need to ensure that the operation's test kit is capable of measuring the disinfectant residual of the pool and that test kit reagents are used in accordance with the manufacturer's specifications |