3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
At the time of inspection ORP reading was below 650 mv. Reading was at 643.
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
At the time of inspection a means of determining rate-of-flow was not found for all water pumps.Replace flow meter with one that is able to read at a lower gpm.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Repeat At the time of inspection emergency device (telephone) was not working.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities.
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 30-March-2022
Comments |
---|
Flow meter was not to the proper range. |