3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Corrected During Inspection Free chlorine residual less than 1 ppm at the time of inspection.
3701-31-04 (B)(4)(a)(ii) / Combined chlorine is tested daily at pool side prior to use
Combined chlorine was not tested daily at pool side prior to use.
Test for combined chlorine prior to bathers entering the water and every 4 hours the pool is open for use. If ACC is in use combined chlorine must be tested every 12 hours while the pool is in use. For spraygrounds and spray features, the combined chlorine must be tested at 1 spray feature every 6 hours the sprayground or spray feature is in use.
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day.
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Total alkalinity was not tested weekly.
Test total alkalinity at least once/week.
3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Cyanuric acid was not tested weekly.
Test for cyanuric acid level at least once/week.
3701-31-04 (B)(4)(b) / Life guard/ CPR/First Aid training certificates are current and available
Life guard/CPR/First Aid training certificates were not available at the time of inspection.
Provide documentation of all training certificates for all lifeguards.
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladders/stairs/steps were not in good repair or were not slip resistant. PIC had ladder blocked from use at the time of inspection.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Gate on perimeter barrier around the swimming pool is not self-closing and self-latching. Correction: All gates or doors of the perimeter barrier shall be self-closing and self-latching to prevent unauthorized entry.
3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Corrected During Inspection Chemical storage room open at the time of inspection. Correction: Ensure chemical storage rooms are closed when not in use by authorized personnel.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 25-July-2022
Comments |
---|
-Ensure 30-60 feet of nylon line is attached to to ring buoy. |