Inspection Information | Facility Name: | MOORE POOL-RECREATION |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 09-August-2021 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 ( D )(6)(a) ORP reading was below 650 mv at 645 mv Have the ACC unit inspected to determined why the ORP is low. |
3701-31-04 (B)(1)(g) Critical Water clarity was not sufficient to see the pool bottom (or Secchi disc). The licensee shall not operate a public swimming pool or portion thereof when an imminent health hazard is present. Do not operate the pool when water clarity is poor. |
3701-31-04 (B)(3) Staff was not trained or knowledgeable in pool operations. Train staff in pool operations, operation of equipment, chemical storage, use and handling and appropriate emergency procedures. |
3701-31-04 (B)(4)(a)(vi) Total alkalinity was not tested weekly. Test total alkalinity at least once/week. |
3701-31-04 (B)(4)(a)(vii) Cyanuric acid was not tested weekly. Test for cyanuric acid level at least once/week. |
3701-31-04 (C)(2) pH was outside the range of 7.2 to 7.8. pH was measured at 8.0 ppm. Treat the pool water so that the pH is within the acceptable range. |
3701-31-04 (C)(5) Water clarity was so poor that the deepest portion of the pool was not clearly visible. Do not operate the pool when water clarity is poor. Improve the water clarity so that the bottom of the pool is clearly visible at all times. |
Comments |
---|
Cyanuric acid was measured at < 30 ppm. WCHD provided the correct form for recording daily pool water testing during the last inspection on 6/2/2021 and again after today's inspection. Facility PIC was also provided with a current copy of the Ohio pool code. Facility has no documented expiration date for the main drain covers. A few items were not observed due to the facility closing the pool during the inspection as a result of an imminent health hazard. The facility chose to close the pool due to poor water clarity. |