Inspection Information | Facility Name: | BOB MOR INC DBA QUALITY INN |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Follow-up |
Inspection date: | 30-August-2019 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 ( D )(6)(a) Repeat ORP reading was below 650 mv at the time of inspection, reading at 455 mv. Have the ACC unit inspected to determined why the ORP is low. |
3701-31-04 (B)(1)(c) Critical Repeat Disinfection residual was less than 1 ppm. Free chlorine was measured to be 0.4 ppm |
3701-31-04 (B)(1)(e) Critical Repeat Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation. |
3701-31-04 (B)(4) Repeat The licensee /authorized representative was not keeping or maintaining operational records. Records had not been kept for over 2 months. All facility records must be maintained and available for review upon request. |
3701-31-04 (C)(2) Repeat pH was outside the range of 7.2 to 7.8. pH was measured at 7.0. Treat the pool water so that the pH is within the acceptable range. |
Comments |
---|
A follow-up was conducted on 8/30/19 to address the critical violations. Free, combined, and total chlorine were not tested due to depleting our reagent supply testing combined chlorine the day before and due to the facility having expired reagents. The pool was still closed upon arrival. Had PIC adjust their chemical feeder set points and calibrate their auto chemical controller. Pool remained closed after the follow-up inspection. Later in the afternoon, the facility called to report readings from their new test kit. All readings were acceptable and facility was told it was ok to resume operating. |