Inspection Information | Facility Name: | WILLIAMS COUNTY FAMILY YMCA |
---|---|
Facility Type: | Pool |
[?] Inspection type: | Standard |
Inspection date: | 05-March-2020 |
Violations: A summary of the violations found during the inspection are listed below. |
3701-31-04 ( D )(6)(a) ORP reading was below 650 mv. ORP reading at the time of inspection was 608 mv. Have the ACC unit inspected to determined why the ORP is low. |
3701-31-04 (C)(2) pH was outside the range of 7.2 to 7.8. pH was measured at 8.0 at the time of inspection. Treat the pool water so that the pH is within the acceptable range. |