[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv, the ORP was 265.
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical The free chlorine was zero.
Resolve this issue before reopening the pool.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 02-August-2021