[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met. The reading on the flow meter was 233 gallons per a minute the required flow rate is 480 gallons per a minute. Resolve this violation.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 24-August-2018

Comments
Water chemistry and safety equipment satisfactory.