3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
Repeat ORP reading was below 650 mv. The ORP was only 515 increase it to the required level.
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04(D)(6)(a)(2) / Pool free chlorine disinfectant residual shall be above 1 ppm.
Critical Repeat Pool free chlorine disinfectant residual was below 1 ppm. The free chlorine was .5 ppm. The maintenance worker had repaired the pump during the inspection..
Do not operate the pool until the chlorine disinfectant residual is at 1 ppm or above.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 08-August-2023
Comments |
---|
No violations were noted at time of inspection. |