[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met. The flow meter read 1654 gpm, resolve this violation.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 02-June-2022

Comments
Note:
managers attended our yearly pool operator training.
Patterson Pools just installed a new auto controller Hayward Cat 4000 and they stated that it was on the ODH approval list to install without an ERN.
The pump was just turned on.