[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv. The ORP was 265 increase to above 650 per code.
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical The free chlorine was zero.
Resolve this violation before reopening the pool.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met. The flow meter read 200 gpm and it needs to be increased to above referenced turn over rate.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 02-August-2021