3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met. The flow meter indicated 40 gallons per a minute this pools required turnover rate is 67 gallons per a minute, Resolve this violation.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 10-July-2020
Comments |
---|
Owner had the pool closed at time of inspection. Owner contacted local pool contracting companies to resolve this issue with the turnover rate. Note:Maintain proper chlorine levels when the pool is open. |