3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met. The follow meter showed 60 gallons per a minute the required turn over rate is 67 gallons per a minute. Resolve this violation.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
3701-31-04 (E)(2)(a)(ii) / A USCG Type IV personal flotation device with 30 -60 foot throw line provided
A USCG Type IV personal flotation device with 30 -60 foot throw line was not provided at the unguarded pool. Replace the damaged rope as discussed.
Provide a proper floatation device at all times.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 16-June-2020
Comments |
---|
The pool has not been open fro the season yet. Test and record the results of the vac-alert according to the owners manual. Replace the damaged fence as discussed, I will consult with ODH regarding plain review then I will follow up with you. Water checmistry satisfactory. Covid-19- Advised to set up 6 foot separation around the pool, and to review the guidance document and up grade as needed to comply. |